綜述水電站電氣設(shè)備的故障及排除
綜述水電站電氣設(shè)備的故障及排除
摘要:發(fā)電設(shè)備是一種極其重要的能源轉(zhuǎn)換設(shè)備,它的故障對(duì)國民經(jīng)濟(jì)有著直接影響。因此電氣設(shè)備的故障分析和處理是非常重要的,文章主要從幾個(gè)方面分析了水電站電氣設(shè)備故障及其處理方法。具有重要的實(shí)際意義。
Abstract: the power generation equipment is a very important energy conversion devices, its fault have a direct impact on the national economy. So electrical equipment failure analysis and treatment is very important, the paper mainly from several aspects the electrical equipment failure analysis of hydropower station and its processing method. Has the important practical significance.
近年來我國電事業(yè)隨著國民經(jīng)濟(jì)的飛速發(fā)展得到了迅猛的增長,特別是中小型水電站星羅棋布,投運(yùn)或在建的電站不斷涌現(xiàn)。保證水電站電氣設(shè)備安全、可靠、長周期地運(yùn)行,加強(qiáng)水電站電氣設(shè)備的維護(hù),迅速及時(shí)地排除設(shè)備故障,延長設(shè)備的使用壽命,是每一個(gè)電氣運(yùn)行和維護(hù)人員的主要課題。
1水電站調(diào)速器引發(fā)的故障處理
1.1電液轉(zhuǎn)換器故障。故障表現(xiàn)為在調(diào)速器上電或機(jī)組正常運(yùn)行過程中,電液轉(zhuǎn)換器不振,對(duì)控制、操作命令液壓隨動(dòng)系統(tǒng)無反應(yīng)。根據(jù)運(yùn)行經(jīng)驗(yàn),此種故障的原因主要有兩方面: 一是機(jī)械故障,因長期運(yùn)行油質(zhì)不凈或其本身異物導(dǎo)致犯卡造成的。出現(xiàn)此種故障后,操作面板顯示屏顯示的工作狀態(tài)正常,但電液轉(zhuǎn)換器不振。此時(shí),可將調(diào)速器的手/自動(dòng)工作方式互相切換幾次,或檢修時(shí)將其活塞往復(fù)運(yùn)動(dòng)幾次或進(jìn)行清洗,可消除故障; 二是電器故障,因電液轉(zhuǎn)換器工作回路斷線或主控單元故障造成的。此時(shí)應(yīng)使機(jī)組在手動(dòng)方式下運(yùn)行,故障待停機(jī)后檢修處理。
1.2開度、開限反饋表指示不符。在運(yùn)行過程中,其故障表現(xiàn)為: 其一,當(dāng)調(diào)速器處于自動(dòng)運(yùn)行狀態(tài)時(shí),開度指示與導(dǎo)葉實(shí)際開度不符,且在當(dāng)前水頭下開度與出力不符,平衡表指示不平衡,其二,當(dāng)調(diào)速器處于手動(dòng)運(yùn)行狀態(tài)時(shí): 開度指示超前于開限指示,并且在當(dāng)前水頭下開度與出力不符,導(dǎo)葉開度與開限指示值相符。此類故障的出現(xiàn)多是機(jī)械部位故障所致。此類故障出現(xiàn)后,要妥善對(duì)待,停機(jī)后一般可將故障迅速排除。
1.3主控單片機(jī)故障。調(diào)速器在運(yùn)行過程中發(fā)生單片機(jī)啟動(dòng)后不能按預(yù)定的程序正常執(zhí)行而形成的“死機(jī)”故障。故障出現(xiàn)后,面板顯示屏顯示不正常,電液轉(zhuǎn)換器不振,調(diào)速器不能正常工作。據(jù)運(yùn)行經(jīng)驗(yàn)分析,此種故障的產(chǎn)生是由于單片機(jī)復(fù)位控制電路故障造成的。處理時(shí),可對(duì)單片機(jī)進(jìn)行再上電或進(jìn)行復(fù)位操作,保證機(jī)組正常運(yùn)行發(fā)電,待停機(jī)檢修時(shí)輔以示波器及萬用表等對(duì)故障電路進(jìn)