狀態(tài)檢修與高壓試驗人員應(yīng)對策略
狀態(tài)檢修與高壓試驗人員應(yīng)對策略
摘要:電力系統(tǒng)中運行的電氣設(shè)備長期遭受著天氣、溫度、雷擊、操作過電壓及自身發(fā)熱的作用, 在這些因素的作用下, 絕緣將會逐漸老化, 導(dǎo)致放電擊穿, 造成系統(tǒng)停電。文中介紹了根據(jù)設(shè)備的絕緣狀況,并根據(jù)設(shè)備的具體情況制定相應(yīng)的解決方案
關(guān)鍵詞:狀態(tài)檢修;在線監(jiān)測;在線檢測;絕緣;預(yù)防性試驗
Abstract: in the power system, the electrical equipment of the operation had been suffering from the weather, temperature, lightning, operating over-voltage and their own fever role in under the effect of these factors, insulation would gradually ageing, lead to discharge breakdown, cause system outage. This paper introduces the status of the insulation according to equipment, and according to the specific situation of the equipment, formulate the corresponding solutions
Keywords: the state overhaul; Online monitoring; Online detection; Insulation; Preventive test
1綜述
狀態(tài)檢修, 顧名思義就是根據(jù)電力設(shè)備的健康狀況進(jìn)行檢修, 它是以電力設(shè)備狀態(tài)監(jiān)測及故障診斷技術(shù)為基礎(chǔ)的、通過對電氣絕緣的試驗和各種特性的測量, 了解及評估設(shè)備在運行過程中的狀態(tài), 從而能早期發(fā)現(xiàn)故障的技術(shù)。狀態(tài)檢修, 是電力行業(yè)未來的發(fā)展方向, 廣東電網(wǎng)的某一個供電局第一個狀態(tài)檢修試驗點,F(xiàn)在, 定期預(yù)防性試驗和檢修已在電力系統(tǒng)形成制度, 對減少和防止事故的發(fā)生起到了很好的作用。但是, 預(yù)防性試驗是離線的, 也有很多不足之處, 主要表現(xiàn)在如下幾個方面: 1)試驗時需要停電。2)試驗時間集中、工作量大。3)試驗電壓低,診斷的有效性值得研究。現(xiàn)行的變電設(shè)備中有很大部分的運行相電壓為110/√3-500/√3kv, 而傳統(tǒng)的診斷方法的試驗電壓一般在10kv及以下, 即試驗電壓遠(yuǎn)低于工作電壓。由于試驗電壓低, 不易發(fā)現(xiàn)缺陷。由于是周期性定期檢查, 不是連續(xù)的隨時監(jiān)測, 絕緣仍有可能在試驗間隔期內(nèi)發(fā)生故障。4)由于是定期的預(yù)防性試驗和檢修, 設(shè)備狀態(tài)即使良好時,按計劃也需進(jìn)行試驗和維修, 造成人力物力財力的浪費, 甚至可能因拆卸組裝過多而造成損壞, 即造成所謂過度檢修。
2 狀態(tài)監(jiān)測
目前正在發(fā)展起以狀態(tài)監(jiān)測和故障診斷為基礎(chǔ)的狀態(tài)檢修?梢詫﹄娏υO(shè)備進(jìn)行在線狀態(tài)監(jiān)測, 及時取得各種信息。對這些信息進(jìn)行處理和綜合分析后, 根據(jù)其數(shù)值的大小及變化趨勢, 可對絕緣的可靠性隨時作出判斷, 從而能早期發(fā)現(xiàn)潛伏的故障。在線監(jiān)測與故障診斷技術(shù)的特點是可以對電力設(shè)備在運行狀態(tài)下進(jìn)行連續(xù)或隨時監(jiān)測與判斷, 故可避免上述預(yù)防性試驗的缺點。如在線監(jiān)測發(fā)現(xiàn)事故隱患后, 就可以在離線狀態(tài)下進(jìn)行徹底的全面檢查。采取狀態(tài)監(jiān)測與故障診斷技術(shù)后, 可以使預(yù)防性試驗檢修向預(yù)知性檢修即狀態(tài)檢修過渡, 從“ 到期必修”